Fault Codes

Fault
No.

Fault Indication and Corrective Action

03

Power Loss Fault

Monitor incoming AC line for low voltage or line power
interruption.

04

UnderVoltage Fault

Monitor incoming AC line for low voltage or line power
interruption.

05

OverVoltage Fault

Bus overvoltage caused by motor regeneration. Monitor
incoming AC line for excessive voltage. Extend the decel
time or install dynamic brake module or external capaci-
tor module.

06

Motor Stall Fault

Longer acceleration time or a reduced load required.

07

Motor Overload Fault

Reduce motor load until drive output current does not
exceed the current set by P42 - [Motor Overload
Current]. Reduce P38 - [Boost Select].

08

Over Temperature Fault

Clear blocked or dirty heat sink fins. Check ambient tem-
perature. Check for blocked or non-operating fan.

11

Operator Error

Clear fault. Do not remove keypad under power.

12

Overcurrent FauIt

Check short circuit at the drive output or excessive load
conditions at the motor.

13

Software Overcurrent Fault

A longer acceleration time, reduced load, or removal of
motor shaft blockage is required.

Parameter 07 - [Active Fault]

Fault Number

IMPORTANT: This publication is designed as a reference
tool. The 160 SSC User Manual (publication 0160-5.15) must
be consulted for more detailed information about parameters,
faults and hazards of personal injury.

160 SSC™ Variable
Speed Drive

Quick Reference
Series C, FRN 7.xx

Publication 0160-5.16 – June, 2000

P/N 189339 (02)

Supersedes October, 1998

20

Drive Overload Fault

Clear blocked or dirty heat sink fins. Check ambient tem-
perature. Check for blocked or non-operating fan.
Reduce motor load current.

32

EEPROM Fault

Reset EEPROM using P56 - [Reset Functions]. Set to 1.
Cycle Power

33

Max Retries Fault

Repair system fault.

36

Incompatible Fault

Check the wiring between the drive and the motor.
Check the motor for a grounded phase.

38

Phase U Fault

Check the wiring between the drive and motor. Check
motor for grounded phase.

39

Phase V Fault

Check the wiring between the drive and motor. Check
motor for grounded phase.

40

Phase W Fault

Check the wiring between the drive and motor. Check
motor for grounded phase.

41

UV Short Fault

Check the motor and external wiring to the drive output
terminals for a shorted condition.

42

UW Short Fault

Check the motor and external wiring to the drive output
terminals for a shorted condition.

43

VW Short Fault

Check the motor and external wiring to the drive output
terminals for a shorted condition.

46

Intermittent Power Output Fault

Check the wiring between the drive and motor. Check
the motor for more than one shorted output.

48

Reprogram Fault

Clear fault.

These faults have an auto reset feature. This feature automatically clears overvolt-
age, undervoltage and overtemperature faults 1 second after the fault condition is
removed. Refer to P51 - [Restart Time].