Restoring Factory Defaults

This example will show you how to reset the factory defaults of the drive.

Action

Description

Display

20. Press the Down Key to advance to the b parameter group.

b - -

21. Press the SELect key to enter into the b parameter group.

b 01

22. Press the Up Key to scroll through the parameters until parameter b84 -

[Reset Functions] is displayed.

b 84

23. Press the SELect Key to view the parameter value stored in parameter b84 -

[Reset Functions] and verify that it is set to 01. If it is not 01, use the UP key to
change the value to 01, then press the Enter key.

Note: The defaults will be reset to the values determined by parameter b85 -
Factory Default Select].

01

24. Press the SELect Key to exit the parameter value back to the parameter

number without changing the stored value.

b 84

25. Press and hold the SELect, Up, Down and Stop Keys for 3 seconds.

NOTE: The keys can be pressed and held in any sequence, but the Stop Key

MUST be the last key held.

b 84

26. Release the Stop Key and continue to hold the SELect, Up and Down Keys

until the display begins to blink. Release the remaining keys. When this is
done, 0.0 will be displayed (this is parameter d01 - [Output Frequency]).

00

”Blinking”

0.0

+

+

+