Parameters & Programming

26

1

U = 60 Hz default settings, K = 50 Hz default settings. Settable using

P

b85 – [Factory Default Select]

Parameter
Number

Parameter Name / Description

Min./Max
Range

Units

Factory

Defaults

DC Brake

U

1

K

1

A51

[DC Brake Enable]
Used to enable/disable DC injection braking
Settings:

00=Disabled
01=Enabled

00/01

Numeric Value

00

00

A52

[DC Brake Start Frequency]
Sets the frequency at which the DC brake will
become active.

0.5/10.0

0.1Hz

10.0

10.0

A53

[DC Brake Wait Time]
Sets the time the drive will wait after PA52 -
[DC Brake Start Frequency] before applying
PA54 - [DC Hold Voltage].

0.0/5.0

0.1 seconds

0.0

0.0

A54

[DC Hold Voltage]
Sets the level of DC braking voltage in percent
of PA82 - [Base Voltage].

0/100

1% of drive

rating

0

0

A55

[DC Hold Time]
The time that PA54 -[DC Hold Voltage] is
applied to the motor after PA53 - [DC Brake
Waiting Time] has expired.

0.0/60.0

0.1 seconds

0.0

0.0

Operating Frequency Range

U

1

K

1

A61

[Upper Frequency Limit]
This is an upper frequency limit similar to PA04 -
[Maximum Frequency] except that it can be
set lower than PA03 - [Base Frequency]. A
value of 0.0 will disable this parameter.

Output Frequency

0.5/360.0

0.1Hz

0.0

0.0

A62

[Minimum Frequency]
Lowest frequency the drive will output
continuously.

Refer to diagram in

PA61 – [Upper Frequency Limit].

0.0/360.0

0.1Hz

0.0

0.0

A63

[Skip Frequency 1]
Sets a frequency at which the drive will not output
continuously.

0.0/360.0

0.1Hz

0.0

0.0

A64

[Skip Frequency Band 1]
Sets the bandwidth around PA63 -[Skip
Frequency 1]. The bandwidth is 2x PA64 –
[Skip Frequency Band 1] with ½ the band
below and ½ the band above PA63 - [Skip
Frequency 1].

0.0/10.0

0.1Hz

0.5

0.5

A65

[Skip Frequency 2]
Sets a frequency at which the drive will not output
continuously.

0.0/360.0

0.1Hz

0.0

0.0

A66

[Skip Frequency Band 2]
Sets the bandwidth around PA65 -[Skip
Frequency 2]. The bandwidth is 2x PA66 -
[Skip Frequency Band 2] with ½ the band
below and ½ the band above PA65 - [Skip
Frequency 2].

0.0/10.0

0.1Hz

0.5

0.5

Output Frequency

Frequency Command

A61

A62

Advertising