Setting Up Measurements Chapter 3

You must check the Also collect phase data checkbox in the Collection
Specification dialog box so the data collector collects phase at orders.

6.

Select the storage specification.

The first measurement definition is now complete.

7.

If you want to create more than one measurement, copy the measurement
definition by selecting the correct row and choosing Edit > Copy.

8.

Move down to the next empty row in the measurement definition
spreadsheet, and choose Edit > Paste to paste the copied measurement
definition.

9.

Edit the new measurement definition by changing the measurement filter.

10.

Select a band filter centered on the next order.

11.

Repeat steps 6 and 7 to create measurement definitions for the desired
orders.

You can then include these measurement definitions in a list and load it to
the data collector. Remember that you must have a trigger signal to collect
magnitude and phase at an order.

Typical Magnitude and Phase Measurement Definitions

The Measurement Definition pane for one through four orders might look like

Magnitude and Phase Measurement Definitions on page 91

. Note that all

measurement definitions have the same units and collection specification.

Figure 17 - Magnitude and Phase Measurement Definitions

The following table shows the collection specification for Mag & Phase.

Table 27 - Collection specification for mag & phase measurement definitions

Transducer

Window

Signal Detection

Fmax

Lines

Phase

Order Norm?

Averages

Accelerometer

Hanning

Peak

500 Hz

400

Yes

Yes

4 linear