Setting up collection specifications, Edit the measurement definitions – Rockwell Automation 1441-DYN25-Z Dynamix 2500 Data Collector User Manual

Page 75

Advertising
background image

Rockwell Automation Publication 1441-UM001B-EN-P - September 2012

75

Setting Up Measurements Chapter 3

Setting Up Collection
Specifications

Measurement definitions are controlled in part by the collection specification
(Setup > Collection). You select the collection specification when you set up the
measurement definition. You can create new collection specifications based on
your specific measurement by choosing Setup > Collection.

Figure 13 - Collection Specification Dialog Box

The transducer specification used in the collection specification includes both
the base unit and the calibration value.

Edit the Measurement Definitions

The Emonitor software does not allow you to change some of the information for
a measurement definition after you collect data for that measurement definition.
This prevents you from collecting and then comparing data with different
measurement definition selections. You cannot edit the Data Type or Units
columns in the Measurement Definition dialog box after you collect data You
can, however, change the Collection, Filter, and the Storage columns for a
measurement definition after collecting data.

The figures in a typical measurement setup in the following sections refer to
making selections in these dialog boxes. For example, a table for STD (HZ) 2000
collection specification would look like this.

Measurement
Input Type

Measurement
Window Type

Measurement
Maximum
Frequency

Measurement
Zoom

Measurement
Resolution

Measurement Signal
Detection Type

Number and Type of
Averages

Orders Track

Magnitude and Phase
Measurement at
Orders

Magnitude and Phase
Measurement at
Orders

IMPORTANT

Changing the collection specification can make it difficult to
compare data after the change with data before the change.

Table 19 - STD (Hz) 2000 collection specification

Transducer

Window

Signal Detection

Fmax

Lines

Phase?

Order Norm?

Averages

Accelerometer

Hanning

Peak

2 kHz

400

No

No

4 linear