Measurement Input Types

The input type is part of the transducer specification (Setup > Calibration). The
transducer is part of the collection specification (Setup > Collection). You select
the collection specification when you set up the measurement definition.

The Emonitor software and the Dynamix 2500 data collector support the
following input types.

Follow these to specify an input type.

1.

Select Setup > Calibration.

2.

Choose the correct Dynamix 2500 data collector from the Collector list.

3.

Assign Input types, Calibration, and appropriate Units to the transducer.

Figure 14 - Transducer Calibration dialog box

Table 20 - Transducer specification in STD (Hz) 2000 collection specification

Name

Base Unit

Input Type

Units

DC Offset

Accelerometer

Acceleration

ICP Accel

g’s

0

Input Type

Description

ICP Accel

Use for ICP accelerometers requiring current from a power
supply.

AC Coupled

Use for AC voltage measurements and non-ICP accelerometers.

DC Coupled

Use for DC voltage measurements. This includes numeric
(process) measurements taken from a DC voltage output.

Manual Entry

Use for numeric (process) measurements where you enter the
value for the measurement with the data collector keyboard.