The transducer specification in the Mag & Phase collection specification is
shown in the table below.

The filter specifications are shown in the table below:

Numeric (Process) Measurement Definitions

The Emonitor software and the Dynamix 2500 data collector support numeric
measurement definitions. This topic lists the unique characteristics of the
Dynamix 2500 data collector that you may need to know when setting up and
collecting numeric data.

Measurements Units Not Supported in the Dynamic 2500 Data Collector

You can make a numeric measurement definition for any available

measurement unit by setting Data Type to ‘Numeric.’

Numeric measurement definitions with Input type set to ‘DC Coupled’

with units not supported by the Dynamix 2500 data collector map to units
of USER (eus). The input type is part of the transducer specification that
you select for the collection specification. This results in a process (DC)
voltage measurement in the Dynamix 2500 data collector.

For a list of support measurement units, see

Measurement Units on

page 74

.

Full Scale Values for Numeric Measurements in the Dynamix 2500 data
collector

The full scale value in the Dynamix 2500 data collector for a numeric

measurement is defined as ten times the value of the alarm or the baseline
measurement.

If no alarm or baseline measurement exists for the measurement in the data

collector, the Dynamix 2500 data collector assumes a full scale value of
10,000.

Table 28 - Transducer specification in mag & phase collection specification

Name

Base Unit

Input Type

Units

Calibration Value

DC Offset

Accelerometer

Acceleration

ICP Accel

g’s

100

0

Table 29 - Filter specifications in mag & phase measurement definitions

Name

Low Cutoff

High Cutoff

Data collector filter type

1st Order

0.8 Orders

1.2 Orders

None

2nd Order

1.8 Orders

2.2 Orders

None

3rd Order

2.8 Orders

3.2 Orders

None

4th Order

3.8 Orders

4.2 Orders

None