Rockwell Automation 1492 Modicon 800-to-1756 I/O Swing-arm Conversion System User Manual

Page 4

Advertising
background image

(4)

10000021923 (Version 00)

b) Refer to Figures 2c and 2d. Remove the 800 I/O housing from the control cabinet.

3) Install the 1492 I/O Conversion System Base-plate in the Control Panel

a) Refer to Figure 3a. Place the 1492 conversion base-plate into the control cabinet at the location previously used by the 800 I/O housing. The

conversion base-plate panel mounting bolt hole locations match those of the 800 I/O housing.

b) Refer to Figure 3b. Securely fasten the base-plate to the control panel so as not to exceed the torque value of the bolts selected. NOTE: The

bolts you select will depend on what was used to mount the 800 I/O housing.

4) Install the 800 I/O Swing-arms into the Conversion Modules

a) Remove the appropriate conversion module from its carton. Ensure the functional capability of the 1492 conversion module, as indicated on its

label (example: Figure 4A), meets the conversion requirements for the specific I/O slot.

II. Conversion Steps

Figure 2c

Figure 2d

Figure 3a

Figure 4a

Figure 3b

Before installing the conversion system base-plate into the control panel ensure you follow the system grounding guidelines found in
Rockwell Automation Publication 1770-4.x Industrial Automation wiring and Grounding Guidelines. Follow PLC chassis mounting
information.

There is a label on the 1492 conversion module to indicate which 800 to 1756 I/O module it is capable to convert. Also refer to Appendix B for
a conversion list.

NOTICE

NOTICE

Advertising