II. Conversion Steps


d) Repeat steps 9a through 9b for all remaining conversion module/cable assemblies until all conversions are complete.
e) Recheck that all cables are fully engaged into the mating connectors and that all of the cable slide latch assemblies tabs are locked on each

conversion module. Ensure the 1756 terminal blocks are secured to the 1756 I/O module.

f) Ensure all analog cable ground wires are secured to a 1756 chassis mounting screw. (Refer to Figure 9c) A lug is provided on each analog cable

for this purpose.

g) Refer to Figure 9d, Secure the cover-plate to the base-plate by using the M5 screws supplied with the system (recommended torque 2 Nm)

System Testing Before Applying Power

Before applying power to the system, check continuity from the field wiring terminal block (typically at the bottom of the control panel) to the 1756 I/O
module terminal block. This should be done for several points of each I/O module to ensure connection of the conversion system.