Rockwell Automation 1492 1771-to-1756 I/O Swing-arm Conversion System User Manual

Page 4

Advertising
background image

(4)

b) Refer to Figures 2b and 2c. Remove the 1771 I/O Chassis from the control cabinet.
NOTE: In this example the conversion modules were left in the 1771 chassis.

2) Remove the 1771 I/O Chassis from the Control Cabinet

a) Refer to Figures 2a. Loosen (do not remove) the hardware which attach the 1771 I/O Chassis to the control cabinet enough to remove
the chassis. This mounting hardware will be used to mount the conversion system base plate in Section 3.

3) Install the 1492 I/O Conversion System Base-plate in the Control Panel

a) Refer to Figure 3a. Place the 1492 conversion base-plate into the control cabinet at the location previously used by the 1771 I/O chassis. The

conversion base-plate panel mounting bolt hole locations match those of the 1771 I/O chassis.

b) Refer to Figure 3b. Securely fasten the base-plate to the control panel so as not to exceed the torque value of the mounting hardware. NOTE: The

hardware you select will depend on what was used to mount the 1771 I/O chassis.

II. Conversion Steps

Figure 2b

Figure 2c

Figure 3a

Figure 3

b

Figure 2a

Before installing the conversion system base-plate into the control panel ensure you follow the system grounding guidelines found in
Rockwell Automation Publication 1770-4.x Industrial Automation wiring and Grounding Guidelines. Follow PLC chassis mounting
information.

NOTICE

10000060110 (Version 00)