Brake Fault Contact Monitoring

For all brake module ratings a fault contact has been provided to provide a
remote output signal. Should a brake fuse fail or the brake thermostat trip,
the brake fault contact will open. Interconnection wiring for remote brake
monitoring is provided in the Wiring Schemes section.

Brake Fuses

All brake modules are internally fused to protect brake components. When
replacing brake fuses, use only the type and size specified below.

Brake Module Jumper Settings

For the Mounting Requirements shown previously as well as the Wiring Schemes,
there can be only one master brake module to control dynamic braking. When
multiple brake modules are used, only one brake module can serve as the master
brake to control the remaining slave brake modules.

Dynamic Brake Fuse

Fuse Type

Rating

WA018
WB009
WC009

F1

&

F2

F1

&

F2

F1

&

F2

Ferraz Shawmut

A60Q or Equivalent
A60Q or Equivalent
A60Q or Equivalent

30A, 600V
15A, 600V
15A, 600V

WA070
WB035
WC035

F1

&

F2

F1

&

F2

F1

&

F2

Ferraz Shawmut

A70QS or Equivalent
A70QS or Equivalent
A70QS or Equivalent

125A, 700V
60A, 700V
60A, 700V

WA115
WB110
WC085

F1

&

F2

F1

&

F2

F1

&

F2

Ferraz Shawmut

A70QS or Equivalent
A70QS or Equivalent
A70QS or Equivalent

200A, 700V
200A, 700V
200A, 700V

BRAKE MODE

SLAVE MASTER

1

(2)

(3)

W1

Slave/Master Jumper Set to Master

BRAKE MODE

MASTER SLAVE

1 (2)(3)

W1

BRAKE MODE

SLAVE MASTER

(2)(1)

(3)

W1

Cat. No.

WA018
WB009

WC009

Cat. No.

WA070
WB035

WC035

Cat. No.

WA115
WB110

WC085

BRAKE MODE

SLAVE MASTER

W1

1

(2)

(3)

BRAKE MODE

SLAVE MASTER

(2)(1)

(3)

W1

Slave/Master Jumper Set to Slave

BRAKE MODE

MASTER SLAVE

1 (2)(3)

W1

Cat. No.

WA018
WB009

WC009

Cat. No.

WA070
WB035

WC035

Cat. No.

WA115
WB110

WC085

Input Voltage Jumper Set to 460V

VOLTAGE SELECT

380V 460V

1

(2)

(3)

W2

VOLT SELECT

380V 460V

(2)(1)

(3)

W2

Cat. No.

WB009

Cat. No.

WB035
WB110

Master Brake Module
Jumper Settings

For the master brake module,
leave slave/master jumper W1
factory set to master (jumper
positions 1

&

2).

Slave Brake Module
Jumper Settings

For each slave module, reset
jumper W1 to slave (jumper
positions 2

&

3).

Input Voltage Jumper Settings

Set jumper W2 on 460V models to
correspond to the nominal drive input
voltage. Setting the jumper between
positions 1

&

2 will select an input voltage of

415/460 volts. Setting the jumper between
positions 2

&

3 will select an input voltage of

380 volts.

Only models WB009, WB035

&

WB110 have input voltage jumpers.