Heavy duty dynamic braking 29 – Rockwell Automation 1336_F_E_T_S SERIES A CHOPPER BRAKE MODULE User Manual
Page 29
Heavy Duty Dynamic Braking
29
1336-5.65 — March, 2007
WA070, WB035 and WC035 Terminal Block, Fuse and Jumper Locations
Fuse F1
Fuse F2
BRAKE MODE
SLAVE MASTER
1
W1
Slave/Master
Jumper W1
BRAKE MODE
SLAVE MASTER
W1
VOLT SELECT
380V 460V
1
W2
Brake Frame Ground
(Connect to Earth Ground)
GND
BARCODE
Brake Module Board
DS1
DS1
DC Power ON Light
DS2
Brake ON Light
DS2
E12
E11
E9
E10
1
2
3
4
5
6
Terminal Block TB1
Max/Min Wire Size = 8.4
/
0.8 mm
2
(8
/
18 AWG)
Max Torque = 1.81 N-m (16 lb.-in.)
Terminals E9-E12
Max/Min Wire Size = 33.6
/
2.1 mm
2
(2
/
14 AWG)
Max Torque = 3.96 N-m (35 lb.-in.) for 5.3-2.1 mm
2
(10-14 AWG)
4.52 N-m (40 lb.-in.) for 8.4 mm
2
(8 AWG)
5.09 N-m (45 lb.-in.) for 21.2-13.3 mm
2
(4-6 AWG)
5.65 N-m (50 lb.-in.) for 33.6 mm
2
(2 AWG)
VOLT SELECT
380V 460V
1
W2
Input Voltage Select
Jumper W2
(WB035 Units Only)
1