User configurable items – Rockwell Automation 1609-S350ES Uninterruptible Power Supply - 350VA User Manual

Page 6

Advertising
background image

41063-285-01 (1)

990-2955 05/2006

User Configurable Items

The UPS settings are adjusted through PowerChute software.

Storage

Store the UPS covered in a cool, dry location with the battery module(s) fully charged.
At 5° to 86° F (–15° to 30° C), charge the UPS battery module every six months.
At 86° to 113° F (30° to 45° C), charge the UPS battery module every three months.

Installing/Replacing the Battery Module

This UPS has an easy-to-replace, hot-swappable battery module. The corresponding replacement battery module is 1609-500SBAT.

Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the

replacement procedure.
For instruction, see applicable steps in Battery Connection.

Troubleshooting

Access the troubleshooting guide for this UPS through PowerChute software.

Function

Factory Default

User Selectable Choices

Description

Automatic
Self-Test

Every 14 days (336
hours)

• Every 7 days

(168 hours)

• On start up only
• No self-test

Set the interval at which the UPS will execute a self-test.

UPS ID

UPS_IDEN

Up to eight characters
(alphanumeric)

Uniquely identify the UPS (i.e. server name or location) for
network management purposes.

Date of Last Battery
Replacement

Manufacture Date

mm/dd/yy

Reset this date when you replace the battery module.

Minimum Capacity Before

Return from Shutdown

0 percent

• 0%
• 15%
• 30%
• 45%

• 60%
• 75%
• 90%

Specify the percentage to which battery module(s) will be

charged following a low battery shutdown before powering
connected equipment.

Voltage Sensitivity

High sensitivity

High sensitivity
Medium sensitivity
Low sensitivity

The UPS detects and reacts to line voltage distortions by

transferring to battery operation to protect the connected
equipment.
In situations of poor power quality, the UPS may frequently

transfer to battery operation. If the connected equipment can
operate normally under such conditions, reduce the
sensitivity setting to conserve battery capacity and service

life.

Alarm Delay Control

Enable

• Enable
• Mute
• Disable

Mute ongoing alarms or disable all alarms permanently.

Shutdown Delay

90 seconds

• 0 s
• 90 s
• 180 s
• 270 s

• 360 s
• 450 s
• 540 s
• 630 s

Set the interval between the time when the UPS receives a

shutdown command and actual shutdown.