Dimensions – Rockwell Automation 1414-IPZxxxxx_CPZxxxxx_CPDxxxxx Differential Air Pressure Transmitter User Manual

Page 10

Advertising
background image

10

Differential Air-pressure Transmitter

Publication 1414-IN011B-EN-P - July 2010

Dimensions

Protection circuitry

Reverse voltage protected and output limited

Output signal

4…20 mA (2-wire), 0…5V DC or 0…10V DC (3-wire) Pin jumper

selectable

Current output drive capability

400 Ω maximum @ 24V DC

Voltage output drive capability

2 KΩ minimum for 0…5V DC signal 10 KΩ minimum for 0…10V DC

signal

Zero adjustment

Pushbutton auto-zero

Wiring connections

Screw terminal block (14…22 AWG)

Pressure Connections

Barbed ports for 4.32 mm (0.170 in.) ID flexible tubing

Conduit Connection

Access hole for ½ in. NPT conduit or cable gland

Enclosure

High Impact Black ABS, plenum rated with optional gasket

127 mm x 84 mm x 53 mm (5.00 in. W x 3.3 in. H x 2.1 in. D)

Weight

159 grams (5.6 oz)

Optional Display

3½ digit, 10.16 mm (0.4 in.) digit height

Technical Specifications - Differential Air-pressure Transmitter

Attribute

1414-IPZ10FODAA, 1414-IPZ10FNDAA, 1414-IPD10FNRAA,
1414-CPZ10FODAA, 1414-CPZ10FNDAA, 1414-CPD10PNRAA

(2.11 in.)

53.6mm

(3.32 in.)

84.3mm

(4.56 in.)

115.8mm

Airflow