6

Differential Air-pressure Transmitter

Publication 1414-IN011B-EN-P - July 2010

The input pressure range is set by moving two jumpers to the appropriate range. The available
ranges are marked 1…8 on the circuit board. The two jumpers must be set to the same range or
incorrect readings result. The pressure ranges are shown in the following chart:

Available Differential Air-pressure Transmitters

Low Pressure Transducer

Jumper selectable pressure range

Description

Commercial

Industrial,
cc-pcb

1

2

3

4

Room differential

w/4-20mA±2.5”,

±5.0”,0-5”,0-10”

WC

1414-CPZ10FVRAA

±2.5 in.

±5.0 in.

0…5 in.

0…10 in.

Room differential

w/4-20mA±5.0”,

±10.0”,0-10”,0-20

” WC

1414-CPZ10FRRAA

±5.0 in.

±10.0 in. 0…10 in. 0…20 in.

Room differential

w/4-20mA &

LCD±2.0”,

±4.0”,0-4”,0-8”

WC

1414-CPD10PNRAA 1414-IPD10FNRAA ±2.0 in.

±4.0 in.

0…4 in.

0…8 in.

Static differential

w/4-20mA & duct

probe±2.0”,

±4.0”,0-4”,0-8”

WC

1414-CPZ10FNDAA 1414-IPZ10FNDAA

Static differential

w/4-20mA & duct

probe±3.0”,

±6.0”,0-6”,0-12”

WC

1414-CPZ10FODAA

1414-IPZ10FODAA

±3.0 in.

±6.0 in.

0…6 in.

0…12 in.