5-2

Monitoring and Troubleshooting

1503-UM051D-EN-P – June 2013

Contactor Status

The Contactor Status is indicated with a yellow LED that is off until

a CLOSE command is received. The LED will stay on if the

contactor closes properly, until the contactor is opened.

Contactor Status output relay has a normally open contact. The

contact is open when the contactor is open (LED off), and closed

when the contactor has received a close command (for 200

milliseconds) or if it is closed (LED on).

Series B Design

Additional module states are indicated with the LED as per Table 5.B.

Table 5.A – IntelliVAC Status Indication (Series A design)

Parameter

Conditions

LED State

Relay Contact State

• rated supply voltage

and

• valid configuration

Green

Closed

• undervoltage

or

• contactor fault

or

• invalid configuration X

or

• internal fault

Red Y

Open

Module Status

Y

• insufficient supply voltage

Off

Open

• rated supply voltage

and

• close command present [

and

• contactor closed

Yellow

Closed

Contactor

Status

• insufficient supply voltage

or

• close command absent [

or

• contactor open

Off

Open

X

Applies only to power-up condition.

Y

Fault is reset by cycling control power.

Z

If a contactor close command is applied and then removed in less than 500 milliseconds, the

IntelliVAC may fault and the module status LED will turn red. To clear the fault, module power has to

be removed and reapplied.

[

For mechanical latch contactors a close command does not need to be maintained for the contactor

to remain closed (resulting in a yellow state for contactor status).