5-4

Monitoring and Troubleshooting

1503-UM051D-EN-P – June 2013


Table 5.C – Module Troubleshooting

Problem or Trip Indicated

Indication of the following conditions

Possible Solutions

• Motor Protection activated
• Both Status LEDs ‘Off’

• Investigate and reset
• Check Control Power
• Loose connections in control circuit
• Verify IntelliVAC power input plug is in place

and properly seated

• Verify internal control fuse has not opened

(Refer to Figure 4.1 for location)

• Module Status LED ‘Red’ upon power up

(Series A)

• IntelliVAC faulted. Cycle control power to

reset. Replace IntelliVAC if unsuccessful.

• Module Status LED ‘Red’ upon power up

(Series A)

• Module Status ‘Red Flash 1’ upon power up

(Series B)

• Improper setting of dip switches. Check

settings and cycle control power.

Contactor does not energize

• Loose connection in control circuit.

• Verify contactor auxiliary set up. Reference

Publication 1502-UM052A-EN-P (400A) or

1502-UM051B-EN-P (800A) – Auxiliary

Contact Set-up Procedure.

• Verify circuit continuity (is contactor plug

connected properly?)

• Module status LED ‘Red’ and Contactor

Status LED ‘Off’ (Series A)

• Coil damaged or connections are loose.

Repair and cycle control power.

• Auxiliary Contact Assembly improperly

adjusted. Reference Publication 1502-

UM052A-EN-P (400A) or 1502-UM051B-EN-P

(800A) – Auxiliary Contact Set-up Procedure.

Cycle control power to reset.

• Undervoltage fault (no TDUV), control voltage

dipped below trip point. Cycle control power

to reset. Verify voltage levels are 110 to 240

VAC, 110 to 250VDC

• Module status LED ‘Red’ and Contactor

Status LED ‘Off’ (Series A)

• Module status LED ‘Green’ and Contactor

Status LED ‘Red Flash 1’ (Series B)

• Armature Plate obstructed from closing to coil

face. Verify no foreign material behind the

armature plate. Cycle control power to reset.

Contactor closes momentarily and

will not reclose.

• Both status LEDs ‘Off’

• Check internal control fuse. Verify IntelliVAC

operation in test mode before applying Medium

Voltage. (Refer to Fig. 4.1 for location.)