Typical contactor drop-out times, Appendix – Rockwell Automation 1503VC IntelliVAC Contactor Control Module User Manual

Page 41

Advertising
background image

Appendix

A

1503-UM051D-EN-P – June 2013

Typical Contactor Drop-out Times

The contactor drop-out times shown in the following table are typical

values used when the power fuses are provided as part of a complete

MV controller from Rockwell Automation. The recommendations

are based on Ferraz Shawmut power fuses. Other fuse types may

require alternate drop-out time settings.

Table A.1 – Contactor Drop-out Times

Fuse Rating

Contactor Drop-out Time (msec)

Voltage

Current

400A

800A

2R

3R

4R

6R

9R

12R

18R

19R

50

24R

100

32R

240

38R

™

50

48X

™

75

57X

™

200

2 x 24R

™

100

2 x 32R

™

240

< 5000

2 x 38R

™

240 *

20E

30E

40E

50E

65E

80E

100E

125E

150E

175E

200E

250E

300E

50

350E

75

400E

100

450E

130

500E

™

50

600E

™

75

750E

™

200

< 5000

900E

™

240 *

™

Fuse not suitable for use with 400A contactor.