Commands – Rockwell Automation 1403-DM_LM_MM Powermonitor II Instruction Sheet User Manual

Page 46

Advertising
background image

4-10

General Operation

1403-IN001A-US-P

Commands

Table 4.3 displays the commands for the
Powermonitor II. The gray scale indicates which
commands are available through the Display Module,
the Smart Communication Card, or both.

Display Module and Smart Communication Card

Display Module Only

Smart Communication Card Only

Table 4.3 Commands

Parameter

Description

Range

Force Relay #1 and #2

Forces Relay #1 and #2 to a known state in which the relay
remains at that state until the force is removed.

1 = Energize
2 = De-energize
4 = No Force (Automatic)

Clear Min/Max Log

Resets the Min/Max log with the current real time metering
information.

No
Yes

Clear Snapshot Log

Clears all entries in the Snapshot log buffer.

No
Yes

Clear kWH Counter

Resets the kWH counter to zero.

No
Yes

Clear kVarH Counter

Resets the kVarH counter to zero.

No
Yes

Set kWH Counter

Sets the kWH counter to the user specified value. (0 to clear)

-999.9x10

9

to 999.9x10

9

Set kVarH Counter

Sets the kVarH counter to the user specified value. (0 to clear)

-999.9x10

9

to 999.9x10

9

Clear Status Input #1 to #4
Counter

Resets Status Input #1 to #4 Counter to zero.

No
Yes

Clear Battery Usage
Counter

Resets the Battery Usage Counter to zero.

No
Yes

Restore Factory Defaults

Restores all of the Powermonitor II configuration parameters with
the factory default values.

No
Yes

Clear Hold of Oscillograph
Data

(1)

Allows the user to enable oscillography when the oscillography
type is set to Hold.

No
Yes

Trigger an Oscillograph

1

Allows the user to manually trigger a simultaneous 7 Channel 2-
Cycle and 2 Channel 12-Cycle oscillograph.

No
Yes

Set Harmonic Analysis
Channel Request

1

Specifies the particular input channel for harmonic analysis
information to be returned through the Smart Communication
Card.

1 = Phase 1 Voltage
2 = Phase 1 Current
3 = Phase 2 Voltage
4 = Phase 2 Current
5 = Phase 3 Voltage
6 = Phase 3 Current
7 = Phase 4 Current

Set Oscillography Channel
Request

1

Specifies the particular input channel for an oscillogram to be
returned through the Smart Communication Card.

1 = 2 Cycle Phase 1 Voltage
2 = 2 Cycle Phase 1 Current
3 = 2 Cycle Phase 2 Voltage
4 = 2 Cycle Phase 2 Current
5 = 2 Cycle Phase 3 Voltage
6 = 2 Cycle Phase 3 Current
7 = 2 Cycle Phase 4 Current
8 = 12 Cycle Channel A
9 = 12 Cycle Channel B

Select Setpoint Number

Specifies the particular setpoint information to be returned through
the Smart Communication Card.

1 to 20

(1) Available on 1403-MM only.