Metering

Voltage/Current

Table 4.4 displays the Voltage and Current Metering
information provided by the Powermonitor II. The
gray scale indicates which parameters are available

through the Display Module, the Smart
Communication Card, or both.

Display Module and Smart Communication Card

Display Module Only

Smart Communication Card Only

Table 4.4 Voltage and Current Metering

Parameter

Description

Range

Units

Phase 1 L-N Voltage

RMS line to neutral voltage of phase 1.

0 to 999.9x10

22

Volts

Phase 2 L-N Voltage

RMS line to neutral voltage of phase 2.

0 to 999.9x10

22

Volts

Phase 3 L-N Voltage

RMS line to neutral voltage of phase 3.

0 to 999.9x10

22

Volts

3-Phase Average L-N Voltage Average RMS line to neutral voltage of phase 1, 2, and 3. 0 to 999.9x10

22

Volts

Phase 1 L-L Voltage

RMS line to line voltage between phase 1 and 2.

0 to 999.9x10

22

Volts

Phase 2 L-L Voltage

RMS line to line voltage between phase 2 and 3.

0 to 999.9x10

22

Volts

Phase 3 L-L Voltage

RMS line to line voltage between phase 3 and 1.

0 to 999.9x10

22

Volts

3-Phase L-L Voltage

Average RMS line to line voltage between phase 1, 2, and
3.

0 to 999.9x10

22

Volts

Auxiliary Voltage

(1)

AC or DC auxiliary voltage input RMS voltage.

0 to 999.9x10

22

Volts

Phase 1 Current

RMS current of phase 1.

0 to 999.9x10

22

Amps

Phase 2 Current

RMS current of phase 2.

0 to 999.9x10

22

Amps

Phase 3 Current

RMS current of phase 3.

0 to 999.9x10

22

Amps

3-Phase Average Current

Average RMS current of phase 1, 2, and 3.

0 to 999.9x10

22

Amps

Phase 4 (Neutral) Current

RMS current of phase 4, also known as neutral current.

0 to 999.9x10

22

Amps

Frequency

The frequency of the voltage.

0 to 132

Hertz

Phase Rotation

The phase rotation of a 3-phase system

None
ABC
ACB

N/A

Voltage Positive Sequence

Magnitude of positive sequence voltage in a 3-phase
system.

0 to 999.9x10

22

Volts

Voltage Negative Sequence

Magnitude of negative sequence voltage in a 3-phase
system.

0 to 999.9x10

22

Volts

Current Positive Sequence

Magnitude of positive sequence current in a 3-phase
system.

0 to 999.9x10

22

Amps

Current Negative Sequence

Magnitude of negative sequence current in a 3-phase
system.

0 to 999.9x10

22

Amps

Voltage Unbalance

The ratio between the negative and positive voltage
sequence in a 3-phase system.

0 to 100

Percent

Current Unbalance

The ratio between the negative and positive current
sequence in a 3-phase system.

0 to 100

Percent