Connect power and equipment to the ups, Front panel, 120 v model depicted – Rockwell Automation 1609-U500 Industrial Uninterruptible Power Supply User Manual

Page 3

Advertising
background image

4

Front Panel

Connect Power and Equipment to the UPS

Hardwiring should be performed by a qualified electrician. Use appropriate size wires.

1. The UPS features a transient voltage surge-suppression (TVSS) screw

located on the front panel.

The TVSS screw is used for connecting the ground lead on surge suppression devices such as telephone

and network line protectors.

Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery

power.

2. Hardwire the UPS.

In 230 V applications the UPS must be protected with a circuit breaker that complies with

European standards for branch rated protection per the country of installation.

In 208 V applications, the 1609-U500E must be protected by a dual pole, 10 A branch rated

circuit breaker with UL489 rating.

The 120 V 1609-U500N has supplementary circuit breaker protection. The unit should be

protected by a single pole, 15 A branch rated circuit breaker with a UL489 rating. Allen-Bradley

part number 1492-MCAA115 is suggested. Ensure that the branch circuit breaker is off prior

to wiring the unit.

3. Connect equipment to the UPS.
4. Add optional accessories to the SmartSlot located on the front panel.
5. Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all connected

equipment is switched on.

6. Press the

button on the front panel to start the UPS.

The battery charges to 90% capacity during the first four hours of normal operation.

Do not expect full battery run capability during this initial charge period.

7. For optimal computer system security, install PowerChute

 monitoring software included with the UPS.

PUSH

TO

RESET

1 EPO

2 EPO COM

3 NC

4 COM

5 NO

6 NC

7 COM

8 NO

LOW

BATTERY

ON

BATTERY

INPUT

208/220-240V~ 50/60Hz, 7A MAX

OUTPUT

23

325W, 2.7A MAX

0V~ 50/60Hz, 500VA

L

N

L

N

LINE

NEUTRAL

GROUND

LINE

NEUTRAL

GROUND

Test

120 V model depicted.