User Configurable Items

User Configurable Items

UPS settings

Settings are adjusted through PowerChute

 software or optional Network Management Card.

Function

Factory

Default

User Selectable

Choices

Description

Automatic
Self-Test

Every 14 days
(336 hours)

• Every 7 days

(168 hours)

• On start up only
• No self-test

Set the interval at which the UPS will execute a
self-test.

UPS ID

UPS_IDEN

Up to eight characters
(alphanumeric)

Uniquely identify the UPS (i.e. server name or
location) for network management purposes.

Date of Last
Battery
Replacement

Manufacture
Date

mm/dd/yy

Reset this date when you replace the battery
module.

Minimum Capacity
Before Return from
Shutdown

0 percent

• 0%
• 15%
• 30%
• 45%

• 60%
• 75%
• 90%

Specify the percentage to which batteries will
be charged following a low battery shutdown
before powering connected equipment.

Voltage Sensitivity

High sensitivity

High sensitivity
Medium sensitivity
Low sensitivity

The UPS detects and reacts to line voltage
distortions by transferring to battery operation
to protect the connected equipment.
In situations of poor power quality, the UPS
may frequently transfer to battery operation. If
the connected equipment can operate normally
under such conditions, reduce the sensitivity
setting to conserve battery capacity and service
life.

Alarm Delay
Control

Enable

• Enable
• Mute
• Disable

Mute ongoing alarms or disable all alarms
permanently.

Shutdown Delay

90 seconds

• 0 s
• 90 s
• 180 s
• 270 s

• 360 s
• 450 s
• 540 s
• 630 s

Set the interval between the time when the UPS
receives a shutdown command and actual
shutdown.