1204 Terminator (Class 1, Division 2)

3

Specifications

The following specifications are provided for the Terminator Option.

1

The drive PWM carrier frequency that you choose affects the heat dissipation and the surface temperature
of the terminator.

Heat Dissipation

This chart is based on an ambient temperature of 45 degrees C.

Category

Specifications

Input power

380-600V, Three-Phase

Maximum Drive Carrier
Frequency

1

TFA1 – 6 kHz
TFB2 – 2 kHz

Refer to “Drive Programming” on page 9 for additional information.

Ambient temperature

0-40 degrees C (32-104 degrees F)

Humidity

5-95% non-condensing

Atmosphere

Class 1, Division 2

Heat dissipation

1

Refer to the heat dissipation table below.

Enclosure type

IP65 (NEMA Type 4x)

Hazardous
Environment Rating

T3 (200

°

C); Groups A, B, C, D

Agency certification

U.L., C-UL

Altitude derating

Full rating 0-1000 meters (0-3280 feet)

Ambient

Temperature

Limit

Altitude

m

(ft)

40

30

35

0

4,000

(13,200)

3,000

(9,900)

2,000

(6,600)

1,000

(3,300)

degrees C.

Drive
Frequency

Length

meters (feet)

1204-TFA1 Terminator

1204-TFB2 Terminator

460 Volts + 10%

600 Volts + 10%

460 Volts + 10%

600 Volts + 10%

Watts

Heatsink

°

Watts

Heatsink

°

Watts

Heatsink

°

Watts

Heatsink

°

6 kHz

91 (300)

210W

142

°

C

220W

150

°

C

Must Use 2 kHz

183 (600)

250W

160

°

C

260W

169

°

C

4 kHz

91 (300)

170W

125

°

C

180W

133

°

C

183 (600)

180W

130

°

C

210W

138

°

C

2 kHz

91 (300)

80W

81

°

C

100W

95

°

C

200W

139

°

C

290W

182

°

C

183 (600)

90W

88

°

C

140W

104

°

C

250W

160

°

C

360W

200

°

C