1204 Terminator (Class 1, Division 2)

3. You must allow at least 152.4 mm (6 in.) on each side of the unit

and 304.8 mm (12 in.) on the top and bottom of the unit for
proper air circulation.

4. If your system consistently runs at line voltages above nominal

and you are mounting the terminator in a high-traffic area where
the potential for contact is high, you should place a shroud of
expanded metal or mesh screen around the terminator. The shroud
should not restrict air flow to the terminator, nor should it be
closer than 152.4 mm (6 in.) to the terminator at any point.

5. Connect the red, white and black cable conductors to the

corresponding three-phase motor leads/terminals.

6. Attach the green cable conductor to the motor ground that is

connected directly to the drive PE terminal.

Front View

Top View

Allen-Bradley

Motor Terminator

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

304.8 mm

(12.0 in.)

304.8 mm

(12.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

DANGER

CAN CAUSE SHOCK,

BURNS, OR DEATH

DISCONNECT AND LOCKOUT

ALL POWER SOURCES

BEFORE SERVICING

SURFACES

MAY BE HOT

ALLOW TO COOL

BEFORE SERVICING

Assembled in Mexico

See Instruction Manual For Mounting Instructions

Bulletin 1204–TFXX Series A
AC Drive HP ZZZZ
Voltage WWWW VAC
Max. Carrier Freq. Y KHz
Type 4X Enclosure
Hazardous Locations
Class I, Division 2
Groups A, B, C, D
Temperature Code T3 (200˚ c)

UL

®

C

US

LISTED

IND. CONT. EQ.

FOR USE IN HAZ. LOC.

8AA4

!

ATTENTION: The terminator surfaces may be hot enough
to cause serious burns. If your system consistently runs at
line voltages above nominal, you should place a shroud
around the terminator to prevent accidental exposure.

Front View

Top View

Allen-Bradley

Motor Terminator

Shroud

Shroud

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

152.4 mm

(6.0 in.)

DANGER

CAN CAUSE SHOCK,

BURNS, OR DEATH

DISCONNECT AND LOCKOUT

ALL POWER SOURCES

BEFORE SERVICING

SURFACES

MAY BE HOT

ALLOW TO COOL

BEFORE SERVICING

Assembled in Mexico

See Instruction Manual For Mounting Instructions

Bulletin 1204–TFXX Series A
AC Drive HP ZZZZ
Voltage WWWW VAC
Max. Carrier Freq. Y KHz
Type 4X Enclosure
Hazardous Locations
Class I, Division 2
Groups A, B, C, D
Temperature Code T3 (200˚ c)

UL

®

C

US

LISTED

IND. CONT. EQ.

FOR USE IN HAZ. LOC.

8AA4