Table 11 - system event table, Power_on, Informational – Rockwell Automation 1608 HC-DySC User Manual, 200 A User Manual

Page 32: Unit, T_fan_st, T_in_st_1, T_in_st_2, T_in_st_3, External, Auto-resetting

Advertising
background image

32

Rockwell Automation Publication 1608P-UM004A-EN-P - September 2013

Chapter 6

Maintenance

Table 11 - System Event Table

Event

Code

Code Name

Full Name

Severity

Area

Event Description

Event Resolution

1

POWER_ON

DySC Power On

Informational

Unit

Power re-applied to the DySC.

No action needed.

4

T_FAN_ST

Fan Test Start

Informational

Unit

Start acknowledgment of DySC fan test.

No action needed.

5

T_IN_ST_1

Inverter Test (.5 cycles) Start

Informational

Unit

Start acknowledgment of DySC 0.5 cycle inverter test.

No action needed.

6

T_IN_ST_2

Inverter Test (3 cycles) Start

Informational

Unit

Start acknowledgment of DySC 3 cycle inverter test.

No action needed.

7

T_IN_ST_3

Inverter Test (5.5 seconds) Start

Informational

Unit

Start acknowledgment of DySC 5.5 second inverter test.

No action needed.

9

EXTERNAL

External Inhibit

Auto-Resetting

Inverter

Controller is inhibited by another phase controller.

Review event details from other phase controllers.

11

RUN_TO

Inverter Run Time out

Auto-Resetting

Inverter

DySC inverter had a total cumulative runtime of more than rated.

No action needed.

12

LIM_CYCLE

Inverter Limit Cycle Timeout

Auto-Resetting

Inverter

Power was re-applied more than once within a 58 second period.

No action needed.

13

STAT_OT

Static Switch Over-Temperature

User Attention

Static Switch

Static switch heatsink temperature was greater than maximum rating.

Verify ambient temperature is within DySC specification. Check
for damaged fans. Check for dirty or obstructed air filters.

14

OVERLOAD

Overload

User Attention

Unit

Inverter inhibited because load current exceeded maximum rating.

Reduce load. In parallel DySC systems, verify proper current
sharing among slave cabinets.

15

DC_OV

DC Bus Over-Voltage

User Attention

Inverter

Positive or negative half of DC bus voltage exceeded maximum rating.

Verify line voltage is within ratings. Verify proper DySC
application. Call service.

16

CNTRL_UV

Controller Power Under-Voltage

User Attention

Inverter

DySC control power supply is out of tolerance.

Verify DySC is online and line voltage is within ratings. Call
service.

17

OUTPUT_UV

Output Under-Voltage

User Attention

Inverter

DySC output voltage was less than 80% of nominal during sag correction.
Sag condition likely outside of DySC specification.

Verify line voltage is within ratings. Verify proper DySC
application.

18

INV_OC

Inverter Over-Current

User Attention

Inverter

Inverter current exceeded maximum rating during sag correction.

Verify load current is within ratings. Verify mechanical bypass
switch is open. Verify proper DySC application.

19

DC_UV

DC Bus Under-Voltage

User Attention

Inverter

DC bus voltage below operational range.

Verify line voltage is within ratings.
Call service.

20

OUTPUT_OV

Output Over-Voltage

Call Service

Inverter

DySC output voltage was greater than 115% of nominal during sag
correction.

Call service.

25

SYNC_ERR

Line Synchronization Error

Call Service

Inverter

Inverter not synchronized to line when sag detected.

Call service.

31

CONFIG

Configuration Alert

Call Service

Inverter

Controller configuration has changed.

Call service.

32

CNTRL_MEM

Controller Memory Busy

Auto-Resetting

Inverter

Controller is loading new data into Flash memory.

No action needed.

33

UNBALANCE

Start-Up Test: DC Bus Unbalance

Call Service

Inverter

Positive and negative halves of the DC bus did not charge equally during
power up.

Call service.

34

AC_V_CHK

Start-Up Test: AC Voltage Check

Call Service

Inverter

Output voltage was detected out of tolerance during the start-up test.

Call service.

35

ROLL_CALL

Start-Up Test: Controller Roll Call
Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

Advertising