Fuse rating charts, Table 12 - hc-dysc enclosure fuses – Rockwell Automation 1608 HC-DySC User Manual, 200 A User Manual

Page 35

Advertising
background image

Rockwell Automation Publication 1608P-UM004A-EN-P - September 2013

35

Maintenance

Chapter 6

Fuse locations within the HC-DySC cabinet are shown on a label inside the door.

Fuse Rating Charts

Table 12 - HC-DySC Enclosure Fuses

SHOCK HAZARD: Remove all power supplying the HC-DySC before removing
the protective cover to reset the CBA circuit breaker. Replace all covers and
doors before reapplying power to the HC-DySC.

WARNING: Turn the power to the HC-DySC electronics off by placing the Bypass
Switch into BYPASS or opening the branch circuit breaker before replacing any
fuse. Failure to comply with this warning can result in injury or death.

WARNING: The HC-DySC has high voltage remaining up to 30 minutes after
disconnection from the AC line. Touching exposed or disconnected terminals,
cables or parts of the HC-DySC can lead to serious injuries or even death. Wait
for a minimum of 5 minutes before performing any service or testing on the HC-
DySC after power is removed. Keep doors closed until all internal LED indicators
are extinguished.

WARNING: Keep the cabinet doors closed to ensure proper cooling airflow and
to protect personnel from dangerous voltages inside the HC-DySC

IMPORTANT

A qualified electrician must replace the fuses. Open the front cabinet door(s) to
access the fuse holders and fuses.

To maintain protection of the HC-DySC, be sure to replace the fuse with the
same type and rating. These fuses are available through Rockwell Automation
Technical Support.

Fuse Reference

Fuse Location

Fuse Rating

Manufacturer

Part Number

F1, F2, F3

Cabinet: Main Power Input

600A/500V

Mersen A50QS600-4IL

F4, F5, F6

Cabinet: Cross-Coupling Transformer

100A/600V

Mersen AJT100

F7, F8, F9
(3 wire models only)

Cabinet
Neutral Forming Transformer

4A/600V

Mersen TRS4R

F10, F11

Cabinet: Input Control Transformer

1A/600V

Mersen TRS1R

F12, F13

Cabinet: Cross Coupler Auxiliary

2A/600V

Mersen ATQR2

F14, F15

Cabinet: Output Control Transformer

4A/600V

Mersen TRS4R

F16, F17, F18
F20 (4 wire only)

Cabinet: TVSS Input

40kA surge / 600V

Mersen VSP40-2

F19

Cabinet: Input Control Transformer

4A/600V

Bussmann FNQ-R-4

F1, F2

Power Module (x3): Voltage Feedback

2A/600V

Mersen ATQR2

F3

Power Module (x3)

--

Not Field Replaceable

F4, F5, F6, F7

Power Module (x3): Dynamic Brake

20A/600V

Mersen ATM20