COM_VER

Start-Up Test: Communication
Compatibility Mismatch

Call Service

Unit

Firmware communication compatibility problem detected during start-up
test.

Call service.

37

CNFG_TO

Start-Up Test: Controller Configuration
Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

38

CNFG_ERR

Start-Up Test: Controller Configuration
Mismatch

Call Service

Unit

Controller firmware configuration problem detected during start-up test.

Call service.

39

FIRM_TO

Start-Up Test: Controller Firmware
Check Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

40

FIRM_DIFF

Start-Up Test: Controller Firmware
Revision Mismatch

Call Service

Unit

Controller firmware revision mismatch detected during start-up test.

Call service.

41

SRL_TO

Start-Up Test: Controller Serial Number
Check Timeout

Call Service

Unit

Controller communication problem detected during start-up test.

Call service.

42

SRL_DIFF

Start-Up Test: Serial Number Mismatch

Informational

Unit

Controller serial number mismatch detected during start-up test.

No action needed.

44

T_INV_TO

Inverter Test Timeout

Call Service

Unit

Phase control board failed to respond to Comm board's Inverter test.

Call service.

46

DOOR_OPEN

DySC Cabinet Door Open

Manual Reset

Unit

DySC door was opened. Mechanical bypass commanded.

Close door. Manually reset DySC.

47

CRIT_OT

Critical Over-Temperature

Manual Reset

Unit

Internal DySC temperature exceeded maximum rating. Mechanical bypass
commanded.

Verify ambient temperature is within DySC specification.
Check for damaged fans. Check for dirty or obstructed air filters.
Manually reset DySC.

48

FUSE_OPEN

Fuse Open

Call Service

Unit

One of the DySC fuses was detected open. Mechanical bypass commanded.

Call service.

49

OPEN_SCR_A

Open SCR Phase A

Call Service

Static Switch

The SCR on the phase A module was detected open.

Call service.

50

OPEN_SCR_B

Open SCR Phase B

Call Service

Static Switch

The SCR on the phase B module was detected open.

Call service.

51

OPEN_SCR_C

Open SCR Phase C

Call Service

Static Switch

The SCR on the phase C module was detected open.

Call service.

53

DYN_BRAKE

Dynamic Brake Error

Call Service

Unit

A problem was detected with the DySC dynamic brake controller.

Call service.

58

PLC_ERR

Programmable Logic Controller Error

Call Service

PLC

PLC error detected.

Call service.

59

PLC_ST_MM

Programmable Logic Controller State
Mismatch

Call Service

Unit

PLC feedback error detected.

Call service.

Event

Code

Code Name

Full Name

Severity

Area

Event Description

Event Resolution