Operation, maintenance and troubleshooting, User controls and indicators, Led indicators – Rockwell Automation 1608S I-Sense User Manual User Manual

Page 16: Table 3 - green normal led flash codes, Table 4 - red error led flash codes

Advertising
background image

Rockwell Automation Publication 1608S-UM001A-EN-P - July 2013

16

Operation, Maintenance and Troubleshooting Chapter 4

Operation, Maintenance and Troubleshooting

The left-side cover may be removed at any time to access the
communications ports.

User controls and indicators

These user controls and indicators are available:

The i-Sense Management Console (requires an Ethernet connection 
to i-Sense)

The www.igrid.com website (available from any Web browser)

Red and Green LED indicators (see Table 3 and Table 4 below)

RESET push button (located inside left cover)

Heartbeat

push button (located inside left cover)

LED indicators

The LEDs will flash to indicate status; the flash codes are listed in the tables
below. Additional status information is available by connecting to the i-Sense
Management Console via the Ethernet port.

Startup/Confirmation Blink:

At power-up and to confirm a push-button

operation, both LEDs will blink rapidly for a few seconds

Table 3 -

Green NORMAL LED

Flash Codes.

Table 4 -

Red ERROR LED

Flash Codes.

Flash
Rate

Meaning

Off

No Power

1

OK

2

Voltage events captured, waiting to transmit.

3

Voltage deviation event detected, voltage has not yet returned to normal (PQ event in progress).

4

Establishing connection to the i-Grid servers.

5

Connected to the i-Grid servers, uploading PQ event data.

Constant

Not operating properly. Push RESET button

Flash Rate

Meaning/Possible Causes

Off

OK

1

Communication error on the last attempt to contact the i-Grid servers. Will retry the connection after a period of time

2

Ethernet interface is not configured and connected to a network
Ethernet interface is initializing
Network cable is unplugged
Note: Only in Ethernet mode

3

Voltage is low. The i-Sense has not detected an AC signal above 90% nominal on each of the enabled voltage channels

4

Both Ethernet and event detection are not initialized yet (combination of status 2 and 3) Note: Only in Ethernet mode