All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM018A-EN-P — February 2014

5

Bulletin 1606 Switched Mode Power Supplies

4. Input Inrush Current

The power supply is equipped with an active inrush current limitation circuit, which limits the input inrush current
after turn-on to a negligible low value. The input current is usually smaller than the steady state input current.

Inrush current

*)

max.

18A

peak

over

entire

temperature

range

typ.

14A

peak

over

entire

temperature

range

Inrush energy

max.

4A

2

s

over entire temperature range

Inrush delay

typ.

750ms

*) The

charging

current

into

EMI

suppression capacitors is disregarded in the first microseconds after switch-on.

Fig. 4-1

Typical turn-on behavior at nominal

load and 25°C ambient temperature

Output

50mS/DIV

Input

230Vac

48Vdc

Input Current 5A / DIV

5. DC Input

Do not operate this power supply with DC input voltage. Check the 1606-XLE480FP-D instead.

Two 1606-XLE480FP-D units in parallel may be necessary.