Hold-up time – Rockwell Automation 1606-XLS960FE Power Supply Reference Manual User Manual
Page 8
Advertising
All parameters are specified at 48V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
8
Rockwell Automation Publication 1606-RM018A-EN-P — February 2014
Bulletin 1606 Switched Mode Power Supplies
7. Hold-up Time
AC 230V
Hold-up Time
typ.
58ms
at 48V, 10A, see Fig. 7-1
min.
47ms
at 48V, 10A, see Fig. 7-1
typ.
30ms
at 48V, 20A, see Fig. 7-1
min.
24ms
at 48V, 20A, see Fig. 7-1
Fig. 7-1
Hold-up time vs. input voltage
Fig. 7-2
Shut-down behavior, definitions
0
10
20
30
40
60ms
170
190
210
230
250Vac
Input Voltage
Hold-up Time
48V, 10A, typ.
48V, 20A, typ.
48V, 10A, min.
50
48V, 20A, min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage