Power terminal block tb1 designations, Tb1 terminal designations, Input fusing – Rockwell Automation 1305 FRN. 6.XX Reference Guide User Manual

Page 2

Advertising
background image

2

Rockwell Automation Publication 1305-5.2.2 - September 2013

1305 Adjustable Frequency AC Drive

Power Terminal Block TB1
Designations

TB1 Terminal Designations

Input Fusing

Maximum Recommended AC Input Line Fuse UL Class J, T, CC, or BS88 (or equivalent)

GRD

To Motor

Required

Input Fusing

L1

R

L2

S

L3

T

+DC

BRK ➀

(–DC)

T1

U

T2

V

T3

W

AC Input Line

To Motor

Dynamic Brake

Option

Required Branch

Circuit Disconnect

GRD

➀ Connection for Dynamic Brake Resistors for all models except the 200-230 Volt, 0.37

to 0.75 kW (0.5 to 1 HP) drive.

Important: The [DB Enable] parameter must be enabled for proper operation.

➁ For single phase applications, the AC input line can be connected to any two of the

three input terminals R, S, T (L1, L2, L3).

➂ 1305 drives provide Class 10 motor overload protection according to NEC Article 430.

They do not provide speed sensitive overload protection, thermal memory retention
and motor over-temperature sensing according to NEC Article 430.126 (A) (2). If such
protection is needed in the end-use product, it must be provided by additional means.

Important: This drive is not intended for use with single-phase motors.

➃ Ground from drive to motor frame must be an independent continuous insulated wire

run.

Terminals

Description

GRD

Earth ground

R, S, T (L1, L2, L3)

AC input line terminals

+DC, BRK (or -DC)

Dynamic brake option – see the instructions included with option

U, V, W (T1, T2, T3)

Motor connections

ATTENTION: The drive does not provide branch circuit protection.
Specifications for the recommended fuse size and type which provide branch
circuit protection against short circuits are provided below. Branch circuit
breakers or disconnect switches cannot provide this level of protection for drive
components.

Three-Phase
Rating
kW (HP)

Single-Phase
Rating
kW (HP)

Fuse
200…230V Rating

Fuse
380…460V Rating

0.37 (0.5)

0.19 (0.25)

6

3

(1)

(1)

Must be dual element time delay, Bussmann LPJ or equivalent.

0.55 (0.75)

0.37 (0.5)

6

3

(1)

0.75 (1)

0.55 (0.75)

10

6

(2)

(2)

If fuse blowing is a problem, use dual element type fuses.

1.5 (2)

0.75 (1)

15

10

(2)

2.2 (3)

1.5 (2)

25

15

(2)

4.0 (5)

20

(2)