All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

14

Rockwell Automation Publication 1606-RM044A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

14. EMC

The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions.
The CE Mark indicates conformance with the EMC directive 2004/108/EC, the low-voltage directive (LVD) 2006/95/EC
and the RoHS directive 2011/65/EC. A detailed EMC report is available upon request.

EMC Immunity

According generic standards: EN 61000-6-1 and EN 61000-6-2

Electrostatic discharge

EN 61000-4-2

contact discharge
air discharge

8kV
15kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz-2.7GHz

10V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

input lines
output lines
DC-OK signal (coupling clamp)

4kV
2kV
1kV

Criterion A
Criterion A
Criterion A

Surge voltage on input

EN 61000-4-5

L N
L PE, N PE

2kV
4kV

Criterion A
Criterion A

Surge voltage on output

EN 61000-4-5

+ -
+ / - PE

1kV
1kV

Criterion A
Criterion A

Surge voltage on DC-OK

EN 61000-4-5

DC-OK signal PE

1kV

Criterion A

Conducted disturbance

EN 61000-4-6

0.15-80MHz

10V

Criterion A

Mains voltage dips

EN 61000-4-11

0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac

40% of 200Vac
70% of 200Vac

0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms

Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A

Voltage interruptions

EN 61000-4-11

0% of 200Vac (=0V)

5000ms

Criterion C

Voltage sags

SEMI F47 0706

dips on the input voltage according to SEMI F47 standard

80% of 120Vac (96Vac)
70% of 120Vac (84Vac)

50% of 120Vac (60Vac)

1000ms
500ms
200ms

Criterion A
Criterion A
Criterion A

Powerful transients

VDE 0160

over entire load range

750V, 1.3ms

Criterion A

Criteria:

A:

Power supply shows normal operation behavior within the defined limits.

C:

Temporary loss of function is possible. Power supply may shut-down and restarts by itself. The power supply will incur no damage or

hazard.

EMC Emission

According generic standards: EN 61000-6-3 and EN 61000-6-4

Conducted emission
input lines

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22

Class B

Conducted emission
output lines **)

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

limits for DC power port
according EN 61000-6-3 fulfilled

Radiated emission

EN 55011, EN 55022

Class B

Harmonic input current

EN 61000-3-2

fulfilled for class A equipment

Voltage fluctuations, flicker

EN 61000-3-3

fulfilled *)

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

*) tested with constant current loads, non pulsing.
**) for information only, not mandatory for EN 61000-6-3.