1606-xlsred redundancy module – Rockwell Automation 1606-XLS240E, -XLS240EA, -XLS240EC, -XLS240E-D Power Supply Reference Manual User Manual

Page 20

Advertising
background image

All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

20

Rockwell Automation Publication 1606-RM044A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

22.3.

1606-XLSBUFFER24 Buffer Module

er

t.

ures.

This buffer unit is a supplementary device for DC 24V power supplies. It delivers power to bridge typical mains failures

or extends the hold-up time after turn-off
of the AC power. In times when the pow
supply provides sufficient voltages, the
buffer unit stores energy in integrated
electrolytic capacitors. In case of mains
voltage fault, this energy is released again
in a regulated process. One buffer module can deliver 20A additional curren

DC

Buffer

Unit(s)

Power

Supply

Load

AC

+

-

The buffer unit does not require any control wiring. It can be added in parallel to
the load circuit at any given point. Buffer units can be added in parallel to increase
the output ampacity or the hold-up time.


22.4. 1606-XLSRED Redundancy Module

L N PE

+ +

- -

1606-
XLS240E

Power

Supply

Adj

Overload

DCok

24V,10A

Failure

Monitor

24V,10A

Load

optional

I

I

L

N

PE

L N PE

+ +

- -

1606-
XLS240E

Power

Supply

Adj

Overload

DCok

24V,10A

XLSRED

Redundancy

Module

+

-

OUT

+

-

IN 1

+

-

IN 2

The 1606-XLSRED is a dual redundancy module, which includes two

diodes as decoupling devices. It
can be used for various purposes.
The most popular application is to
configure highly reliable and true
redundant power supply systems.
Another interesting application is
the separation of sensitive loads
from non-sensitive loads. This
avoids the distortion of the power
quality for the sensitive loads
which can cause controller fail

1606-

Advertising