Environment – Rockwell Automation 1606-XLS240E, -XLS240EA, -XLS240EC, -XLS240E-D Power Supply Reference Manual User Manual

Page 15

Advertising
background image

All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM044A-EN-P — March 2014

15

Bulletin 1606 Switched Mode Power Supplies

Switching Frequencies

The power supply has three converters with three different switching frequencies
included. Two are nearly constant. The other one is input voltage and load dependent.

Switching frequency 1

35kHz

nearly constant

Switching frequency 2

105kHz

nearly constant

Switching frequency 3

40kHz to 220kHz

input voltage and load dependent



15. Environment

Operational temperature

*)

-25°C to +70°C (-13°F to 158°F)

reduce output power according Fig. 15-1

Storage temperature

-40 to +85°C (-40°F to 185°F)

for storage and transportation

Output de-rating

6W/°C

60-70°C (140°F to 158°F)

Humidity

**)

5 to 95% r.H.

IEC 60068-2-30

Vibration sinusoidal

2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis

IEC 60068-2-6

Shock

30g 6ms, 20g 11ms
3 bumps / direction, 18 bumps in total

IEC 60068-2-27

Altitude

0 to 2000m (0 to 6 560ft)

without any restrictions

2000 to 6000m (6 560 to 20 000ft)

reduce output power or ambient temperature,
see Fig. 15-2
IEC 62103, EN 50178, overvoltage category II

Altitude de-rating

15W/1000m or 5°C/1000m

> 2000m (6500ft), see Fig. 15-2

Over-voltage category

III

IEC 62103, EN 50178, altitudes up to 2000m

II

altitudes from 2000m to 6000m

Degree of pollution

2

IEC 62103, EN 50178, not conductive

*) Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit.
**) Do not energize in the presence of condensation.

Fig. 15-1 Output current vs. ambient temp.

Fig. 15-2 Output current vs. altitude

Allowed Output
Current at 24V

0

-25

0

20

40

2.5

5

7.5

10

12.5

15A

continuous

70°C

60

Ambient Temperature

for typ. 4s

Allowed Output
Current at 24V

0

0

2000

4000

6000m

2.5

5

7.5

10

12.5

15A

continuous

Altitude

for typ. 4s

A... Tamb < 60°C

B... Tamb < 50°C

C... Tamb < 40°C

A

B

C