Terminals and wiring, Reliability – Rockwell Automation 1606-XLE240F-3 Power Supply Reference Manual User Manual

Page 10

Advertising
background image

All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

10

Rockwell Automation Publication 1606-RM031A-EN-P — April 2014

Bulletin 1606 Switched Mode Power Supplies

11. Terminals and Wiring

Input Output

Type

screw terminals

screw terminals

Solid wire

0.5-6mm

2

0.5-6mm

2

Stranded wire

0.5-4mm

2

0.5-4mm

2

American Wire Gauge

20-10 AWG

20-10 AWG

Wire stripping length

7mm / 0.275inch

7mm / 0.275inch

Screwdriver

3.5mm slotted or Pozidrive No 2

3.5mm slotted or Pozidrive No 2

Recommended tightening torque

0.8Nm, 7lb.in

0.8Nm, 7lb.in

Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:

60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.

b) Follow

national installation codes and installation regulations!

c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed, but not required.

12. Reliability

3-Phase operation

3AC 400V

3AC 480V

Lifetime expectancy

*)

122 000h

126 000h

at 48V, 5A and 40°C

249 000h

226 000h

at 48V, 2.5A and 40°C

78 000h

88 000h

at 48V, 6A and 40°C

345 000h

355 000h

at 48V, 5A and 25°C

MTBF

**)

SN 29500, IEC 61709

1 051 000h

1 048 000h

at 48V, 5A and 40°C

1 805 000h

1 799 000h

at 48V, 5A and 25°C

MTBF

**)

MIL HDBK 217F

438 000h

424 000h

at 48V, 5A and 40°C; Ground Benign GB40

585 000h

568 000h

at 48V, 5A and 25°C; Ground Benign GB25

Operation on only 2 legs of
the three phase system

2AC 400V

2AC 480V

Lifetime expectancy

*)

114 000h

120 000h

at 48V, 5A and 40°C

253 000h

234 000h

at 48V, 2.5A and 40°C

76 000h

81 000h

at 48V, 6A and 40°C

322 000h

341 000h

at 48V, 5A and 25°C

MTBF

**)

SN 29500, IEC 61709

1 019 000h

1 023 000h

at 48V, 5A and 40°C

1 765 000h

1 771 000h

at 48V, 5A and 25°C

MTBF

**)

MIL HDBK 217F

437 000h

425 000h

at 48V, 5A and 40°C; Ground Benign GB40

584 000h

569 000h

at 48V, 5A and 25°C; Ground Benign GB25

*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime

expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.

**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a

device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.

Advertising