All parameters are specified at 24V, 2.5A, 230Vac input, 25ªC ambient and after a 5 minutes run-in time unless noted otherwise.

Rockwell Automation Publication 1606-RM031A-EN-P — April 2014

11

Bulletin 1606 Switched Mode Power Supplies

13. EMC

The power supply is suitable for applications in industrial environment as well as in residential, commercial and light
industry environment without any restrictions. The CE Mark indicates conformance with EMC guideline 89/336/EC,
93/68/EC and 2004/108/EC and the low-voltage directive (LVD) 73/23/EC and 2006/95/EC. A detailed EMC report is
available on request.

EMC Immunity

Generic standards: EN 61000-6-1 and EN 61000-6-2

Electrostatic discharge

EN 61000-4-2

Contact discharge
Air discharge

8kV
15kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz-2.7GHz

10V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

Input lines
Output lines

4kV
2kV

Criterion A
Criterion A

Surge voltage on input

EN 61000-4-5

L1

L2, L2

L3,

L1

L3

2kV

Criterion A

Surge voltage on input

EN 61000-4-5

L1 / L2 / L3

PE

4kV

Criterion A

Surge voltage on output

EN 61000-4-5

+

-

+ / -

PE

500V
500V

Criterion A
Criterion A

Conducted disturbance

EN 61000-4-6

0.15-80MHz

10V

Criterion A

Mains voltage dips
(Dips on three phases)

EN 61000-4-11

0% of 380Vac

0% of 480Vac

0Vac, 20ms
0Vac, 20ms

Criterion A
Criterion A

Mains voltage dips
(Dips on two phases)

EN 61000-4-11

40% of 380Vac
40% of 480Vac

70% of 380Vac
70% of 480Vac

200ms
200ms
500ms
500ms

Criterion A
Criterion A
Criterion A
Criterion A

Voltage interruptions

EN 61000-4-11

0Vac, 5000ms

Criterion C

Voltage sags

SEMI F47 0706

Dips on two phases according to section 7.2.
of the SEMI F47 standard

80% of 380Vac
70% of 380Vac

50% of 380Vac

1000ms
500ms
200ms

Criterion A
Criterion A
Criterion A

Powerful transients

VDE 0160

over entire load range

1550V, 1.3ms

Criterion A

Criteria:

A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazard to the power supply

will occur.

EMC Emission

Generic standards: EN 61000-6-3 and EN 61000-6-4

Conducted emission

EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22

Class B, input lines

Radiated emission

EN 55011, EN 55022

Class B

Harmonic input current

EN 61000-3-2

fulfilled

Voltage fluctuations, flicker

EN 61000-3-3

fulfilled

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

Switching frequency

Variable between 50kHz and 140kHz depending on load and input voltage