6 Powermonitor II Lithium Battery

Publication 1403-IN006A-EN-P - February 2009

Install or Replace the Lithium Battery

Follow these steps to remove and install the lithium battery in a Bulletin 1403
Master Module.

1. Remove the closure plate on the top face of the Master Module.

Electrical power is normally connected to the Master Module.

2. Gently pull the retaining tab of the battery extractor from its slot, then unfold

and extend the battery extractor upward or away from the Master Module to
completely expose the battery in its holder.

ATTENTION

This procedure may be conducted with full electrical power applied to the Master
Module. Use extreme caution when installing the lithium battery into your Bulletin 1403
Master Module. Failure to use extreme caution can lead to personal injury or death,
property damage, or economic loss.

ATTENTION

When installing or removing the battery within the Bulletin 1403 Master Module, take
care not to come into contact with metallic surfaces if power is applied.

TIP

For proper operation, the device should not be powered for an extended period of time
without a battery installed.

ATTENTION

Perchlorate material; special handling may apply.

See

http://dtsc.ca.gov/HazardousWaste/perchlorate/

Closure plate

Battery extractor

Lithium battery