Publication 1394-5.11 — December 1999

Installing Your 1394 DC Link Module

5

2. Connect one end of the cable to each 1394-DCLM.

Figure 7

Connecting the Communication Cable to the 1394-DCLMs

3. Secure the cable to the 1394-DCLMs with the screws provided

(4M x 10) using 12-15 lb-in. of torque.

4. Modify the start/stop circuit so system 2 (slave DC link) is wired

in series to system 1 (master DC link). Figure 8 illustrates GMC
or GMC Turbo system modules connected together.

Figure 8

Start/Stop Circuit for Systems Connected Together

Cable End

DC Link
Module

1394 Digital Servo Controller

System Module

Allen-Bradley

DC Link
Module

1394 Digital Servo Controller

System Module

Allen-Bradley

Cable End

24V AC/DC

or

120V AC,

50/60 HZ

STOP

START

CR1

CR1

CR1

M1

DRIVE O.K. RELAY

RATED AT 115VAC, 24VDC,

1A INDUCTIVE

24
25
26
27

DRIVE O.K. RELAY

RATED AT 115VAC, 24VDC,

1A INDUCTIVE

24
25
26
27

1394 SYSTEM MODULE 1

1394 SYSTEM MODULE 2

TB2

TB2

GMC or GMC Turbo

Input Wiring Board

GMC or GMC Turbo

Input Wiring Board