Configuration & PLC Interfacing

Publication 1395–5.37– March, 1999

Message Operation

The READ TREND FILE function is used by a PLC Controller to get
information about the Drive’s trend buffers. This data includes both
the setup information and the data samples for each buffer.

PLC Block Transfer Instruction Data –

Write

Read

Size In Elements:

6

Refer to block information

Processor Type:

PLC-5

PLC-5

Destination Address:

N40:0-5

N40:0-18

Message Structure –

0

PLC Message Write

PLC Message Read

NOTE:

Word 4 of the PLC Message Read instruction is broken down
into two bytes. The High byte contains the status bits

The Low byte contains the Drive message length in bytes.

Header
Word 1

0

Function Code
270

Message Length
12 bytes

Header
Word 2

Header
Word 3

Header
Word 4

0

Header
Word 1

0

Function Code
270

See Note

Header
Word 2

Header
Word 3

Header
Word 4

Data
Word 5

Data
Word 6

See
Block Definition

See Trend
Number

See Block
Number

Data
Word 5

Data
Word 6

Refer to the Drive instruction manual for detailed information on Trend
buffer operation and use.

Sample Time – The rate at which the monitored parameter is
sampled.

Post Samples – The number of samples taken after the trigger
condition is detected.

Year – An integer value representing the year the trigger condition
was detected

Month (1 – 12) – An integer value representing the month the trigger
condition was detected.

Day (1 – 31) – An integer value representing the day the trigger
condition was detected.
Hour (0 – 23) – An integer value representing the hour the trigger
condition was detected.
Minute (0 – 59) – An integer value representing the minute the trigger
condition was detected.

Second (0 – 59) – An integer value representing the second the trigger
condition was detected.