Rockwell Automation 1395 ControlNet Communication Board User Manual
Page 85
8–13
Reference
Publication 1395.5.37 – March, 1999
Parameter 552 – [A>ICN Fault Status]
Parameter 502 – [B>ICN Fault Status]
Use: Displays ICN Fault Status
Parameter Type: Setup
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 255 (FFH)
Default Value: 0
Description: Bit value of 1 indicates presense of Soft Fault condition
Parameter 553 – [ICN Warn Status]
Parameter 503 – [ICN Warn Status]
Use: Displays ICN Warning Status
Parameter Type: Source
Program Terminal Units: None
Minimum Value: 0
Maximum Value: 255 (FFh)
Default Value: 0
Description: Bit value of 1 indicates presense of Warning condition
Bit positions for previous four parameters:
7 6 5 4 3 2 1 0
BIT#
PLC Out of Run
Last State
CNet Comm Loss
CNet Class 1 Close
CNet Class 3 Close
CNet Class 1 Timeout
CNet Class 3 Timeout
CNet Plug Failure
(Fault Status Only)
Note: CNet Plug Failure is a Hard Fault and is not configurable
as a Soft Fault or Warning.