10 ArmorPoint I/O Modules with 8 Configurable 24V DC Points

Publication

1738-IN026B-EN-E - February 2010

In RSLogix5000, the default tag will be AdapterName:SlotNumber:O.Data.
The data type is a SINT.

In RSLogix5000, the default tags will be:

• AdapterName:SlotNumber:C.FilterOffOn
• AdapterName:SlotNumber:C.FilterOnOff

Default Data Map – Product Assembly Instance 34

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Data

Pt 07

Pt 06

Pt 05

Pt 04

Pt 03

Pt 02

Pt 01

Pt 00

Where:

Pt = state of the output point

Default Data Map – Product Assembly Instance 103

Message Size: 8 Bytes

7

6

5

4

3

2

1

0

Data [0]

Group Off2On Input filter

Data [1]

Data [2]

Group On2Off Input filter

Data [3]

Data [4]

FltM 7

FltM 6

FltM 5

FltM 4

FltM 3

FltM 2

FltM 1

FltM 0

Data [5]

FltV 7

FltV 6

FltV 5

FltV 4

FltV 3

FltV 2

FltV 1

FltV 0

Data [6]

IdIM 7

IdIM 6

IdIM 5

IdIM 4

IdIM 3

IdIM 2

IdIM 1

IdIM 0

Data [7]

IdIV 7

IdIV 6

IdIV 5

IdIV 4

IdIV 3

IdIV 2

IdIV 1

IdIV 0

Where:

Filter = 0 to 65000 us (0 = default)

Filter = 0 to 65535 us (1000 = default)

FltM = Fault Mode (0 = Fault Value (default), 1 = Hold Last State)

FltV = Fault Value (0 = OFF (default), 1 = ON)

IdlM = Idle Mode (0 = Idle Value (default), 1 = Hold Last State)

IdlV = Idle Value (0 = OFF (default), 1 = ON)