Environmental Specifications

Attribute Value

Temperature, operating

IEC60068-2-1 (Test Ad, Operating Cold),

IEC60068-2-2, (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20...60 °C (-4...140 °F)

Temperature,
nonoperating

IEC60068-2-1 (Test Ad, Non-operating Cold),

IEC60068-2-2, (Test Bd, Non-operating Dry Heat),

-40...85 °C (-40...185 °F)

Vibration

IEC 60068-2-6 (Test Fc, Operating): 5g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

50g

Operating voltage

11...30V DC

Emissions

CISPR 11: Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 30…2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz

3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±3 kV at 5 kHz on signal ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz...80 MHz