ArmorPoint I/O Modules with 8 Configurable 24V DC Points 9

Publication

1738-IN026B-EN-E - February 2010

1738-8CFGM23

Communicate with Your Module

Read this section for information about how to communicate with your
module.
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s or
scanner’s memory. Each module produces 1 byte of input data and consumes
1 byte of I/O data (scanner Tx).

In RSLogix5000, the default tag will be AdapterName:SlotNumber:I.Data.
The data type is a SINT.

Default Data Map – Product Assembly Instance 4

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Data

Pt 07

Pt 06

Pt 05

Pt 04

Pt 03

Pt 02

Pt 01

Pt 00

Where:

Pt = state of the input point

3

4

5

6

7

8

9

10

11

12

2

1

(view into connector)

Pin 1 - I/O 0

Pin 2 - I/O 1

Pin 3 - I/O 2

Pin 4 - I/O 3

Pin 5 - I/O 4

Pin 6 - I/O 5

Pin 7 - I/O 6

Pin 8 - I/O 7

Pin 9 - Return (Com)

Pin 10 - Return (Com)

Pin 11 - 24V DC

Pin 12 - Chassis