Rockwell Automation 1732D-IBDPM12MND DeviceNet ArmorBlock Network Powered 16-Input Module, Series A I.I. User Manual

Page 11

Advertising
background image

DeviceNet ArmorBlock™ Network Powered 16-input Module 11

Publication 1732D-IN007B-EN-E - November 2011

Indicator Status for Modules

Status

Description

Module status

Off

No power applied to the device.

Green

Device is online and has one or more I/O connections in
established state.

Flashing green

Device needs commissioning due to missing, incomplete, or
incorrect configuration.

Red

Critical fault – device timed out or has an unrecoverable fault.

Flashing red

Recoverable fault – input or output short circuit.

Network status Off

Device is not online:

- Device has not completed dup_MAC-id test.

- Device not powered – check module status indicator.

Green

Device operating normally. As a Group 2 module, it means that the
module is allocated to a master.

Flashing green

Device is online with no connections in the established state.

Red

Critical link failure – failed communications module.

Flashing red

Recoverable fault – an I/O connection has timed out.

I/O status

Off

I/O is not energized or is not valid.

Yellow

I/O is energized and valid.