14 DeviceNet ArmorBlock™ Network Powered 16-input Module

Publication 1732D-IN007B-EN-E - November 2011

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

±2 kV line-earth (CM) on communication ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Emissions

CISPR 11:

Group 1, Class A

Certifications

Certification (when
product is marked)

(1)

Value

c-UL-us

UL-listed Industrial Control Equipment, certified for US and Canada. See

UL File E322657.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

ODVA

ODVA conformance tested to DeviceNet specifications

(1)

See the Product Certification link at

http://www.ab.com

for Declaration of Conformity, Certificates, and other

certification details.

Environmental Specifications

Attribute

Value