Convert analog output data, Compute the analog output – Rockwell Automation 1746-FIO4V SLC 500 Fast Analog I/O/ User Manual User Manual

Page 34

Advertising
background image

Publication 1746-UM009B-EN-P - September 2007

34 Processor and Module Considerations

Convert Analog Output Data

The module converts 16-bit binary values from the output image table
to 14-bit analog output signals and left-justifies the bit code in the
channel word. The output range, decimal representation for the
output range, number of significant bits, and converter resolution are
as shown in the following table.

Compute the Analog Output

Use the following formula to compute the output image-table value
(decimal representation) required for a desired analog-output signal
level (to the output device).

EXAMPLE

For example, if the input image table value is 409 from a 4…20
mA sensor.

Analog Output Data

Module

Output Range

Decimal
Representation
(output image table)

Significant
Bits

Resolution

FIO4I

0…21 mA – 1LSB

0…+32,764

13 bits

2.56348 µA/LSB

0…20 mA

0…+31,208

12.92 bits

4…20 mA

6242…31,208

12.6 bits

FIO4V

–10…+10V dc –
1LSB

–32,768…+32,764

14 bits

1,22070 mV/LSB

0…10V dc – 1LSB

0…32,764

13 bits

0…5V dc

0…16,384

12 bits

1…5V dc

3277…16,384

11.67 bits

Full Scale Input
Full Scale Count

Sensor Signal =

x Input Image Value = 0.00977 x 409 = 4 mA

Full-scale Decimal Representation
Full-scale Output

Output Image Value =

x Desired Signal Level

Advertising