Installing the block i/o, Installing block i/o chapter 3 – Rockwell Automation 1791-IOBB USER MANUAL User Manual

Page 13

Advertising
background image

Installing Block I/O

Chapter 3

3Ć2

When using

Maximum

Network Distance

Baud Rate

Used

Maximum Capacity

and

SLC-5/01 Controller

1747-DSN Scanner module*

7 blocks

230.4K

2,500 cable-feet

SLC-5/02 Controller

1747-DSN Scanner module*

30 blocks

230.4K

2,500 cable-feet

SLC-5/02 Controller

1747-SN Remote I/O

Scanner Module*

16 blocks

57.6K

115.2K

230.4K

10,000 cable-feet

5,000 cable-feet

2,500 cable-feet

* The DH-485 network, which operates independent of the RIO/DIO network, supports up to 30 DH-485 nodes (blocks or 1747-AIC

isolated couplers). The maximum DH-485 network distance is 4,000 cable-feet.

Mounting dimensions for the block I/O module are shown in Figure 3.1.
Mount the blocks horizontally with a minimum of 2” between blocks. This
air gap is necessary to maintain proper cooling air flow through the block.

Figure 3.1

Mounting Dimensions for the Block I/O Module (Cat. No. 1791-IOBA and

-IOBB)

OUTPUT

INPUT

COMM POWER

180mm

7.1"

212mm

8.35"

35mm

1.37"

8mm

0.31"

10mm

0.39"

198mm

7.8"

10mm

0.39"

16mm

0.63"

16mm

0.63"

10829-I

Depth = 84.33mm (3.32")

The operating temperature in the air gap between block I/O modules must
not exceed 55

o

C (151

o

F). The dimensions of the air gap required are

shown in Figure 3.2.