12 POINT I/O™ 5V and 24V Encoder/Counter Modules

Publication 1734-IN005G-EN-E - September 2012

Communicate with Your Module

POINT I/O modules send (consume) and receive (produce) I/O messages. You map these
messages into the processor’s memory.

These modules produce 6 or 10 Bytes of input data (scanner Rx) (status). These modules
consume 1 Byte of I/O data (scanner Tx). Use parameters 11 and 12 to select assembly
101, 102, or 103 for data produced by the modules.

When you send a configuration to the module, check for consistency before applying it.
Monitor the PE bit with your user program to isolate any problems with an improperly
configured module. If the configuration is acceptable, the counter ASIC is disabled while
the ASIC is loaded with new operational parameters. Outputs can turn off during this
reconfiguration.

Default Data Map for 1734-IJ, 1734-IK

Message size: 6 or 10 Bytes

15

14

13

12

11

10 09

08

07

06

05

04

03

02 01

00

Produces
(scanner Rx)

Channel 0 value of present counter state (LSW)

Channel 0 value of present counter state (MSW)

PE

EF

NR

0

0

0

0

0

0

ZS

BS

AS

C1

C0

ZD

0

Where:

LSW = Least significant word

MSW = Most significant word

PE = Programming error

EF = EEPROM fault status

NR = Not ready status bit

ZS = Z input status

BS = B input status

AS = A input status

C1/C0 = Stored data count

ZD = Zero frequency detected

Message size: 1 Byte

07

06

05

04

03

02

01

00

Consumes (scanner Tx)

0

0

0

0

0

VR

CP

CR

Where:

VR = Value reset of stored/accumulated count

CP = Counter preset

CR = Counter reset