General specifications – Rockwell Automation 1734-IK/C POINT I/O 5V and 24V Encoder/Counter Module Installation Instructions User Manual

Page 19

Advertising
background image

POINT I/O™ 5V and 24V Encoder/Counter Modules 19

Publication 1734-IN005G-EN-E - September 2012

On-state voltage, max

See the

Input Derating Curve

diagram.

Input filter selections

Off

10

μ

s

100

μ

s

1.0 ms

10.0 ms

Input frequency, max

1.0 MHz counter and encoder X1 configurations

500 kHz encoder X2 configuration (no filter)

250 kHz encoder X4 configuration (no filter)

General Specifications

Attribute

Value

Terminal base screw torque

0.6 Nm (7 lb-in.)

Module location

1734-TB, 1734-TBS, 1734-TB3, 1734-TB3S wiring base assembly

POINTBus current, max

160 mA

Power dissipation, max

1734-IJ – 1.1 W @ rated load

1734-IK – 1.5 W @ rated load

Thermal dissipation, max

1734-IJ – 3.75 BTU/hr @ rated load

1734-IK – 5.1 BTU/hr @ rated load

Isolation voltage (continuous-voltage
withstand rating)

50V

Type tested @ 1100V DC for 60 s, field-side to system

External DC power

No additional external power required to power module

Dimensions, approx., HxWxD

56.0 x 12.0 x 75.5 mm

(2.21 x 0.47 x 2.97 in.)

Wiring category

(1)

1 – on signal ports

Wire size

0.25…2.5 mm

2

(22…14 AWG) solid or stranded copper wire rated

at 75 °C (167 °F), or greater, 1.2 mm (3/64 in.) insulation max

Weight, approx.

0.36 kg (0.08 lb)

Keyswitch position

2

Enclosure type rating

None (open-style)

IEC temperature code

T4

North American temp code

T4A

(1)

Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication

1770-4.1

.

POINT I/O 5V and 24V Encoder/Counter Module – 1734-IK

Attribute

Value