Specifications – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module/ Instructions User Manual

Page 16

Advertising
background image

16 SLC 500™ RTD/Resistance Input Module

Publication 1746-IN007C-EN-P - December 2002

Specifications

Electrical Specifications

Backplane Current Consumption

100 mA at 5V dc
55 mA at 24V dc

Backplane Power Consumption

1.82W maximum (0.5W at 5V dc, 1.32W at 24V dc)

External Power Supply Requirements

None

Number of Channels

8 (backplane isolated)

I/O Chassis Location

Any I/O module slot except slot 0

A/D Conversion Method

Sigma-Delta Modulation

Input Filtering

Low pass digital filter with programmable notch (filter)
frequencies

Common Mode Rejection
(28 Hz and 50/60 Hz Filter frequencies)

> 120 dB at 50 Hz (28 Hz and 50 Hz filter frequencies)
> 120 dB at 60 Hz (28 Hz and 60 Hz filter frequencies)

Normal Mode Rejection
(between [+] input and [-] input)

65 dB minimum at 50/60 Hz with 50/60 Hz filter
110 dB minimum at 50 Hz with 28 Hz filter
95 dB minimum at 60 Hz with 28 Hz filter

Max. common mode voltage

±1 volt

Max. allowed permanent overload

(1)

(1)

Do not apply a voltage or current to the module.

Volts = ±5V dc; Current = ±5 mA

Input Filter Cut-Off Frequencies

7.80 Hz at 28 Hz filter frequency
13.65 Hz at 50/60 Hz filter frequency
209.6 Hz at 800 Hz filter frequency
1676 Hz at 6400 Hz filter frequency

Calibration

Module autocalibrates at power-up. Periodic calibration (every
5 minutes) can also be enabled.

Isolation

500V ac for 1 minute between inputs and chassis ground, and
between inputs and backplane.
5V dc continuous between channels.